Product Overview
Technical Summary
| Product type | AQ 2xU/I HF analog output module |
|---|---|
| Base module | 6ES7135-6HB00-0CA1 |
| Analog outputs | 2 |
| Output ranges | 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | Up to 16 bit including sign |
| Basic error limit | +/-0.1% relative to output range at 25 °C |
| Supply voltage | 24 V DC; 19.2 V to 28.8 V permissible |
| Current consumption | 45 mA without load; 90 mA max. with 2 channels at 20 mA current output |
| BaseUnits | BU type A0, A1 |
| Diagnostics | Channel diagnostics, diagnostic alarm, wire break, short circuit, group error, overflow/underflow |
| Protection and variant | Conformal coating; color code CC00; -40…+70 °C |
Key Features
- Product designation and variant: SIPLUS ET 200SP AQ 2xU/I HF analog output module with conformal coating, -40…+70 °C, BU type A0 or A1, and color code CC00.
- Analog outputs: 2 analog outputs support 0 to 10 V, 1 V to 5 V, -5 V to +5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA ranges.
- Resolution and accuracy: Resolution is up to 16 bit including sign. Basic error limit at 25 °C is +/-0.1% relative to the output range for voltage and current.
- Supply and consumption: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Current consumption is 45 mA without load and up to 90 mA with 2 channels at 20 mA current output.
- Diagnostics and interfaces: The module has channel diagnostics, diagnostic alarm, supply-voltage monitoring, wire-break detection for current output, short-circuit detection for voltage output, group error, and channel-by-channel overflow/underflow detection.
- Mounting and dimensions: Suitable for BU type A0 and A1; width is 15 mm, height 73 mm, depth 58 mm, and approximate weight 31 g.
Frequently Asked Questions
Which specifications distinguish the 6AG1135-6HB00-7CA1 variant?
Check the SIPLUS ET 200SP AQ 2xU/I HF designation, 2 analog outputs, CC00 color code, conformal coating, 24 V DC supply, and BU type A0 or A1 suitability.
What code and nameplate details should be checked?
Check the complete order number 6AG1135-6HB00-7CA1, product designation AQ 2xU/I HF, base module 6ES7135-6HB00-0CA1, and color code CC00.
What output ranges and resolution does the module have?
It supports the listed voltage and current ranges from 0 to 10 V through 4 mA to 20 mA, with resolution up to 16 bit including sign.
What quantity and destination are needed for a quotation?
Provide the required quantity and destination together with the complete order number for quotation processing.