Product Overview
Technical Summary
| Product type designation | DQ 4×24 V DC/2 A ST |
|---|---|
| Digital outputs | 4 source outputs (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 2 A per channel |
| Maximum current per module | 8 A |
| Usable BaseUnits | BU type A0 |
| Color code | CC02 |
| Conformal coating | -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes) |
| Firmware update | Yes |
| Product lifecycle | Start of final year of support |
Key Features
- Product designation: DQ 4×24 V DC/2 A ST digital output module based on 6ES7132-6BD20-0BA0.
- Digital outputs: 4 source outputs (PNP, current-sourcing); outputs are parameterizable and support short-circuit protection.
- Supply and output voltage: Rated supply voltage: 24 V DC, with a permissible range of 19.2 V to 28.8 V. Rated output voltage: 24 V DC.
- Output current: Rated output current per signal "1": 2 A; maximum current per module: 8 A.
- Diagnostics and isolation: Diagnostics include supply-voltage monitoring, module-wise wire-break and short-circuit detection, group error, and green/red DIAG LED. Isolation between channels and the backplane bus is provided; channels are not isolated from each other.
- Configuration and mounting: FW update possible; usable with BU type A0 and configurable/integrated with STEP 7 TIA Portal from version see entry ID: 109746275. The module is rail-based.
Applications
- Digital output control: The module provides source outputs for controlling digital loads.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Frequently Asked Questions
What does Siemens order number 6AG2132-6BD20-4BA0 identify?
It identifies a SIPLUS ET 200SP DQ 4×24 V DC/2 A ST digital output module based on 6ES7132-6BD20-0BA0.
Which output and supply specifications distinguish this module variant?
It has 4 source outputs (PNP, current-sourcing), a 24 V DC rated supply voltage, a 19.2 V to 28.8 V DC permissible supply range, and 2 A rated output current per channel.
Which BaseUnit and color code should be checked?
Check for usable BaseUnit BU type A0 and color code CC02.
What diagnostics are available?
The module has supply-voltage monitoring, module-wise wire-break and short-circuit diagnoses, group error, diagnostic alarms, and green/red DIAG LED indication.
What details are needed for a quotation?
Provide the complete order number 6AG2132-6BD20-4BA0, required quantity, and destination.