Product Overview
Technical Summary
| Product designation | SIPLUS S7-400 PS 405 10 A |
|---|---|
| Based on | 6ES7405-0KA02-0AA0 |
| Rated DC input | 24 V DC, 48 V DC, 60 V DC |
| Backplane bus output | 5 V DC, maximum 10 A; 24 V DC, maximum 1 A |
| Mains failure stored energy time | 20 ms |
| Input current | 4 A at 24 V DC; 2 A at 48 V DC; 1.6 A at 60 V DC |
| Slots required | 2 |
| Conformal coating | Class 2 according to EN 61086; Type 1 according to EN 60664-3 |
| Operating ambient temperature | -25 °C to 70 °C |
| Installation altitude | Maximum 5 000 m above sea level |
| Connection method | 3x 1.5 mm2, solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm |
Key Features
- Product designation: SIPLUS S7-400 PS 405 10 A based on 6ES7405-0KA02-0AA0.
- DC input: Rated input values: 24 V DC, 48 V DC, and 60 V DC.
- Output supply: 5 V DC output for the backplane bus, maximum 10 A; no base load required. The 24 V DC backplane bus output is maximum 1 A and idling-proof.
- Conformal coating: Conformal coating for printed circuit board assemblies according to EN 61086, Class 2 for high reliability; Type 1 protection according to EN 60664-3.
- Ambient operation: Ambient temperature during operation: -25 °C to 70 °C.
- Installation and protection: Requires 2 slots, has equipment protection class I with protective conductor, and supports installation altitude up to 5 000 m above sea level.
Frequently Asked Questions
What does Siemens order number 6AG1405-0KA02-7AA0 identify?
It identifies a SIPLUS S7-400 PS 405 10 A power supply based on 6ES7405-0KA02-0AA0.
Which input and output ratings should be checked for this MLFB?
Check the rated input values of 24 V DC, 48 V DC, and 60 V DC, plus the 5 V DC backplane bus output with a maximum of 10 A and the 24 V DC backplane bus output with a maximum of 1 A.
What configuration details distinguish this exact variant?
The variant has conformal coating, -25 °C to 70 °C ambient operation, requires 2 slots, and has a Class I equipment protection rating with protective conductor.
Is the backup battery included?
The backup battery is optional.
What details are needed for a quotation?
Provide the complete order number 6AG1405-0KA02-7AA0, required quantity, and destination.