Product Overview
Technical Summary
| Product designation | SINAMICS G120 POWER MODULE PM240-2 |
|---|---|
| Rated power (LO) | 45.00 kW | 60.00 hp |
| Rated power (HO) | 37.00 kW | 50.00 hp |
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Frame size | FSE |
| Degree of protection | IP20 / UL open type |
| Connections | Screw-type terminals on line side, motor end, and DC link |
| Control unit and panel | Without control unit and panel |
| Firmware approval | CU firmware version V4.7 HF8 |
Key Features
- Product designation: SINAMICS G120 POWER MODULE PM240-2, without filter, with an integrated braking chopper.
- Rated power: Output rated power is 45.00 kW | 60.00 hp for low overload and 37.00 kW | 50.00 hp for high overload.
- Supply: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
- Overload ratings: High overload: 200% for 3 s, 150% for 57 s, 100% for 240 s, at -20 … 50 °C. Low overload: 150% for 3 s, 110% for 57 s, 100% for 240 s, at -20 … 40 °C.
- Connections and dimensions: Screw-type terminals are provided on the line side, motor end, and DC link. Dimensions are 551 mm × 275 mm × 237 mm; net weight is 26.00 kg.
- Configuration and protection: Frame size FSE, degree of protection IP20 / UL open type, without control unit and panel. Approved for CU firmware version V4.7 HF8.
Frequently Asked Questions
What product does Siemens order number 6SL3210-1PE28-8UL0 identify?
It identifies a SINAMICS G120 POWER MODULE PM240-2 without filter, with an integrated braking chopper.
Which ratings distinguish the low-overload and high-overload configuration?
Low overload is 45.00 kW | 60.00 hp; high overload is 37.00 kW | 50.00 hp. Their stated ambient temperature ranges are -20 … 40 °C and -20 … 50 °C respectively.
What connection and protection details should be checked?
Check the screw-type terminals on the line side, motor end, and DC link, plus IP20 / UL open type protection and FSE frame size.
What configuration exclusions should be verified before quotation?
This configuration is without a filter, control unit, and panel. Verify the complete order number, required quantity, and destination for quotation.