Product Overview
Technical Summary
| Product designation | SIPLUS ET 200S EM 2AI high speed based on 6ES7134-4GB52-0AB0 with conformal coating |
|---|---|
| Analog inputs | 2 |
| Input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Cycle time, all channels, max. | 0.25 ms |
| Load voltage L+, rated value (DC) | 24 V |
| Resolution with overrange, max. | 16 bit |
| Signal encoder connection | Current measurement as a 2-wire transducer |
| Isochronous mode | Yes |
| Power loss, typ. | 2.5 W |
| Product lifecycle | Product cancellation |
Key Features
- Product designation: SIPLUS ET 200S EM 2AI high speed based on 6ES7134-4GB52-0AB0 with conformal coating.
- Analog inputs: 2 analog inputs with a maximum cycle time of 0.25 ms for all channels.
- Input ranges: Rated current input ranges: 0 to 20 mA and 4 mA to 20 mA; input resistance for 0 to 20 mA is 106 Ω.
- Load voltage L+: Rated value (DC): 24 V. Short-circuit protection and reverse polarity protection are present.
- Signal encoder connection: Connection for current measurement as a 2-wire transducer; shielded cable length is maximum 200 m.
- Diagnostics and separation: Hardware interrupt, wire-break diagnosis at 4 to 20 mA, group error, and overflow/underflow are supported. The analog inputs are electrically separated from the backplane bus and load voltage L+, but not between channels.
Frequently Asked Questions
What does Siemens order number 6AG1134-4GB52-2AB0 identify?
It identifies a SIPLUS ET 200S EM 2AI high-speed module based on 6ES7134-4GB52-0AB0 with conformal coating.
Which specifications distinguish this module variant?
The module has 2 analog inputs, 0 to 20 mA and 4 mA to 20 mA rated input ranges, a 0.25 ms maximum cycle time for all channels, and 16 bit maximum resolution with overrange.
What signal encoder connection is supported?
It supports current measurement as a 2-wire transducer. A shielded cable may be up to 200 m long.
What protection and electrical separation does it have?
Load voltage L+ has short-circuit and reverse polarity protection. The analog inputs are separated from the backplane bus and load voltage L+, but not between channels.