Product Overview
Technical Summary
| Product designation | SIPLUS ET 200S EM 8 DI based on 6ES7131-4BF00-0AA0 |
|---|---|
| Digital inputs | 8 |
| Supply voltage, rated value (DC) | 24 V |
| Input voltage, rated value (DC) | 24 V |
| Input voltage for signal "0" | -30 to +5 V |
| Input voltage for signal "1" | +15 to +30 V |
| Input current for signal "1", typ. | 5 mA |
| Input characteristic curve | IEC 61131, type 1; 2-wire sensors connectable |
| Conformal coating and temperature range | Conformal coating, -25…+70 °C |
| Address space per module, max. | 1 byte |
Key Features
- Product designation: SIPLUS ET 200S EM 8 DI based on 6ES7131-4BF00-0AA0, with conformal coating and -25…+70 °C.
- Digital inputs: 8 digital inputs with a DC input voltage type.
- Rated voltage: Supply voltage rated value (DC): 24 V; input voltage rated value (DC): 24 V.
- Input signal ranges: Signal "0": -30 to +5 V; signal "1": +15 to +30 V.
- Sensor connection: 2-wire sensors are connectable; permissible quiescent current is 1.5 mA max.
- Isolation and diagnostics: Digital inputs are isolated from the backplane bus but not between channels; diagnostics function: No.
Frequently Asked Questions
Which specifications distinguish Siemens 6AG1131-4BF00-7AA0?
It is a SIPLUS ET 200S EM 8 DI based on 6ES7131-4BF00-0AA0, with 8 digital inputs, conformal coating, and -25…+70 °C.
What input voltage ranges should be checked for this MLFB?
Signal "0" is -30 to +5 V, and signal "1" is +15 to +30 V.
Does the module support 2-wire sensors?
Yes. 2-wire sensors are connectable, with a permissible quiescent current of 1.5 mA max.
What cable lengths are supported?
The maximum cable length is 1 000 m for shielded cable and 600 m for unshielded cable.