Product Overview
Technical Summary
| Product type | CPU 1512SP-1 PN |
|---|---|
| Order number | 6AG2512-1DM03-4AB0 |
| Program work memory | 400 kbyte |
| Data work memory | 2 Mbyte |
| PROFINET interfaces | 1 |
| PROFINET ports | 3; 1 integrated + 2 via BusAdapter |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V DC |
| Number of IO Controllers | 1 integrated |
| Number of connectable IO Devices, max. | 128 |
Key Features
- Product designation: SIPLUS ET 200SP CPU 1512SP-1 PN, based on 6ES7512-1DM03-0AB0.
- Memory: 400 kbyte integrated work memory for the program and 2 Mbyte for data; a SIMATIC Memory Card is required.
- PROFINET interface: 1 PROFINET interface with IRT, an integrated 3-port switch, and 25 ns bit performance; a BusAdapter is required for port 1 and port 2.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC.
- Railway and environmental variant: Conformal coating; horizontal installation operating temperature: -40 °C to 70 °C, with +85 °C for 10 min under OT4, ST1/ST2 conditions according to EN 50155.
Applications
- Rail vehicles: The source supports use on rail vehicles under EN 50121-3-2, EN 50121-4, EN 50121-5, EN 50124-1, EN 50125-1, EN 50125-2, EN 50125-3, EN 50155, and EN 61373.
- Stationary industrial systems: The source supports use in stationary industrial systems for biologically, chemically, and mechanically active substances according to EN 60721-3-3.
- Industrial process technology: The source supports use in industrial process technology against chemically active substances according to EN 3, excluding trichlorethylene.
Frequently Asked Questions
Which product designation should be checked for Siemens order number 6AG2512-1DM03-4AB0?
Check that the designation is SIPLUS ET 200SP CPU 1512SP-1 PN and that the complete order number is 6AG2512-1DM03-4AB0.
Which specifications distinguish this CPU variant?
Check the 400 kbyte program work memory, 2 Mbyte data work memory, PROFINET IRT interface with 3 ports, and conformal coating.
What interface and mounting details should be verified?
Verify the 1 PROFINET interface, the integrated port and 2 BusAdapter ports, and the required BusAdapter for port 1 and port 2.
What information is needed for a quotation?
Provide the complete order number, required quantity, and destination.