Product Overview
Technical Summary
| Product designation | SIPLUS S7-300 spare part based on 6ES7321-1FH00-0AA0 |
|---|---|
| Digital inputs | 16 |
| Input type | AC |
| Rated input voltage | 120/230 V AC (47 … 63 Hz) |
| Signal "0" input voltage | 0 to 40V |
| Signal "1" input voltage | 79 to 264V |
| Input current, signal "1", typ. | 6.5 mA; (120 V, 60 Hz), 16 mA (230 V, 50 Hz) |
| Backplane bus input current, max. | 29 mA at 5 V DC |
| Power loss, typ. | 4.9 W |
| Isolation | Between digital inputs and backplane bus: Yes; Optocoupler |
Key Features
- Product designation: SIPLUS S7-300 spare part based on 6ES7321-1FH00-0AA0, with conformal coating.
- Digital inputs: 16 isolated digital inputs for 120/230 V AC.
- Input voltage: Rated input voltage: 120/230 V AC (47 … 63 Hz); signal "0": 0 to 40V; signal "1": 79 to 264V.
- Installation capacity: Horizontal installation: 16 inputs up to 40 °C and 16 inputs up to 60 °C; vertical installation: 16 inputs up to 40 °C.
- Isolation: Isolation between the digital inputs and backplane bus: Yes; Optocoupler. Isolation tested with 4 000 V DC.
- Product lifecycle: Product cancellation.
Frequently Asked Questions
What does 6AG1321-1FH00-7AA0 identify?
It identifies a SIPLUS S7-300 spare part based on 6ES7321-1FH00-0AA0, with conformal coating and 16 isolated AC digital inputs.
Which specifications distinguish this exact configuration?
The configuration has 16 inputs, 120/230 V AC input voltage, a -40…+70 °C range, and a 1x 20-pole connection.
Does this configuration include alarms or diagnostics?
It is without alarms and without a diagnostics function.
How are the digital inputs isolated?
The digital inputs are not isolated between channels; they are isolated from the backplane bus by an Optocoupler.