Product Overview
Technical Summary
| Product designation | SINAMICS Power Module PM240-2 |
|---|---|
| Input supply | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated power, LO | 0.75 kW | 1.00 hp |
| Rated power, HO | 0.55 kW | 0.75 hp |
| Rated current, LO | 2.20 A output; 2.90 A input |
| Rated current, HO | 1.70 A output; 2.60 A input |
| Maximum output current | 3.40 A |
| Output frequency | 0 … 200 Hz for vector control; 0 … 550 Hz for V/f control |
| Connections | Plug-in screw terminals, line side and motor end |
| Protection | IP20 / UL open type |
| Configuration | Without Control Unit and operating unit; CU firmware version V4.6 |
Key Features
- Product designation: SINAMICS Power Module PM240-2 with integrated Class A filter and integrated braking chopper.
- Input supply: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
- Output power: 0.75 kW | 1.00 hp rated power at low overload; 0.55 kW | 0.75 hp at high overload.
- Overload ratings: High overload: 0.55 kW at 200% for 3s, 150% for 57s, and 100% for 240 s at -10 … +50 °C ambient temperature. Low overload: 0.75 kW at 150% for 3s, 110% for 57s, and 100% for 240 s at -10 … +40 °C ambient temperature.
- Connections and mounting: Plug-in screw terminals on the line and motor sides; FSA frame size; dimensions 196 mm H x 73 mm W x 165 mm D.
- Protection and configuration: IP20 / UL open type; supplied without Control Unit and operating unit; released as of CU firmware version V4.6.
Frequently Asked Questions
What does Siemens order number 6SL3210-1PE12-3AL1 identify?
It identifies a SINAMICS Power Module PM240-2 with an integrated Class A filter and integrated braking chopper.
Which ratings should be checked when verifying this MLFB?
Check the 3 AC, 380 … 480 V ±10 % input, 0.75 kW low-overload rating, 0.55 kW high-overload rating, and 3.40 A maximum output current.
Which connection and mounting details distinguish this variant?
It has plug-in screw terminals on the line and motor sides, FSA frame size, and dimensions of 196 mm H x 73 mm W x 165 mm D.
What configuration details should be confirmed before quotation?
Confirm that the configuration is without Control Unit and operating unit, and that it is released as of CU firmware version V4.6.
What quantity and destination are needed for a quotation?
Provide the required quantity and destination for quotation.