Product Overview
Technical Summary
| Product designation | SIPLUS SIMOCODE pro V basic unit 2 |
|---|---|
| Product type designation | SIMOCODE pro V PB |
| Inputs and outputs | 4 digital inputs; 3 monostable relay outputs |
| Thermistor connection | 1 input |
| Communication interface | PROFIBUS DP; maximum transfer rate 12 Mbit/s |
| Control supply | 110 … 240 V AC/DC; 50 Hz or 60 Hz |
| Mounting | Screw and snap-on mounting |
| Operating temperature | -25 … +60 °C |
Key Features
- Product designation: SIPLUS SIMOCODE pro V basic unit 2, product type designation SIMOCODE pro V PB.
- Inputs and outputs: 4 parameterizable digital inputs, including 1 input for thermistor connection, and 3 monostable relay outputs.
- Communication interface: PROFIBUS DP interface with a maximum transfer rate of 12 Mbit/s; connection is a 9-pin SUB-D socket (12 Mbit) / screw terminal (1.5 Mbit).
- Control supply: AC/DC control supply voltage of 110 … 240 V at 50 Hz, 60 Hz, or DC.
- Mounting and dimensions: Screw and snap-on mounting; 111 mm height, 45 mm width, and 124 mm depth.
- Conformal coating and temperature: Conformal coating with an ambient temperature during operation of -25 … +60 °C.
Applications
- Motor management: The source identifies the product as a motor management system and supports motor protection evaluation, overload protection, and parameterizable overload relay control.
- Motor circuit control: Supported circuit functions include direct start, reverse starting, star-delta circuit, star-delta reversing circuit, Dahlander circuit, and pole-changing switch circuit.
- Diagnostics and monitoring: The unit provides diagnostics, data acquisition, active power monitoring, current detection, phase failure detection, voltage detection, and overvoltage or undervoltage detection.
Frequently Asked Questions
What product does Siemens order number 6AG1010-1AU00-4AA0 identify?
It identifies a SIPLUS SIMOCODE pro V basic unit 2 with product type designation SIMOCODE pro V PB.
Which I/O configuration distinguishes this variant?
It has 4 parameterizable digital inputs, 1 input for thermistor connection, and 3 monostable relay outputs.
Which communication interface should be checked for this code?
The interface is PROFIBUS DP with a maximum transfer rate of 12 Mbit/s, using a 9-pin SUB-D socket (12 Mbit) / screw terminal (1.5 Mbit).
Which supply and mounting details should be verified before quotation?
Verify the 110 … 240 V AC/DC control supply, screw and snap-on mounting, and dimensions of 111 mm x 45 mm x 124 mm.