Product Overview
Technical Summary
| Product code | 6AG1135-4FB01-2AB0 |
|---|---|
| Product designation | SIPLUS ET 200S EM 2AQ U |
| Base product | 6ES7135-4FB01-0AB0 |
| Analog outputs | 2 |
| Supported voltage ranges | 1 V to 5 V; -10 V to +10 V |
| Rated load voltage | 24 V DC; from power module |
| Cycle time, all channels, max. | 1.5 ms |
| Resolution with overrange, max. | 14 bit; 1 to 5 V: 12 bit, ±10 V: 13 bit + sign |
| Ambient temperature during operation | -25 °C to 60 °C |
Key Features
- Product designation: SIPLUS ET 200S EM 2AQ U based on 6ES7135-4FB01-0AB0, with conformal coating.
- Analog outputs: 2 analog outputs with supported voltage ranges of 1 V to 5 V and -10 V to +10 V.
- Load voltage: Rated load voltage: 24 V DC, from the power module; reverse polarity protection: Yes.
- Output performance: Maximum cycle time for all channels: 1.5 ms; maximum short-circuit current for voltage output: 25 mA.
- Connections and load: Two-wire and four-wire connections for voltage output; minimum voltage-output load impedance: 1 kΩ; maximum capacitive load: 1 μF.
- Dimensions and weight: 15 mm width, 81 mm height, 52 mm depth, and approximately 40 g weight.
Applications
- Stationary industrial systems: Use in stationary industrial systems against biologically, chemically, and mechanically active substances according to the supplied EN 60721-3-3 classifications.
- Ships and at sea: Use on ships and at sea against biologically, chemically, and mechanically active substances according to the supplied EN 60721-3-6 classifications.
- Industrial process technology: Use in industrial process technology against chemically active substances according to EN 60654-4 and environmental conditions according to ANSI/ISA-71.04.
Frequently Asked Questions
What does the complete 6AG1135-4FB01-2AB0 code identify?
It identifies the SIPLUS ET 200S EM 2AQ U module based on 6ES7135-4FB01-0AB0, with conformal coating and -25…+60 °C ambient operation.
Which specifications distinguish this module variant?
The module has 2 analog voltage outputs, supports 1 V to 5 V and -10 V to +10 V, and has a maximum cycle time of 1.5 ms for all channels.
What connection details should be checked?
Check whether the installation requires a two-wire or four-wire voltage-output connection. Two-wire connection has no compensation of line resistances.
What details are needed for a quotation?
Provide the complete order number, required quantity, and destination so the configuration can be verified for quotation.