Product Overview
Technical Summary
| Product | SIPLUS S7-300 SM 332 8 AO HART |
|---|---|
| Based on | 6ES7332-8TF01-0AB0 |
| Analog outputs | 8 |
| Output ranges | 0 to 20 mA; 4 mA to 20 mA |
| Output type | 0/4–20 mA HART |
| Actuator connection | Two-wire connection |
| Operating temperature | -25…+60 °C |
| Load impedance, max. | 750 Ω with current outputs |
| Resolution, max. | 16 bit |
| Requirement | PCS 7 V7.0, SP1 |
Key Features
- Product designation: SIPLUS S7-300 SM 332 8 AO HART module, based on 6ES7332-8TF01-0AB0.
- Analog outputs: 8 analog outputs with 0 to 20 mA and 4 mA to 20 mA output ranges.
- HART output: Analog output: 0/4–20 mA HART with two-wire actuator connection.
- Operating temperature: -25…+60 °C.
- Conformal coating: The module has conformal coating.
- Diagnostics and functions: Firmware update, HART auxiliary variables, redundancy, local diagnostic buffer with time stamping, and diagnostic alarm are supported. Requirement: PCS 7 V7.0, SP1.
Applications
- Firmware update: Supports firmware update.
- HART auxiliary variables: Supports HART auxiliary variables.
- Local diagnostic buffering: Supports a local diagnostic buffer with time stamping.
Frequently Asked Questions
What does Siemens order number 6AG1332-8TF01-2AB0 identify?
It identifies a SIPLUS S7-300 SM 332 8 AO HART analog output module based on 6ES7332-8TF01-0AB0.
Which specifications distinguish this MLFB variant?
The supplied variant has 8 analog outputs, 0/4–20 mA HART, conformal coating, and a -25…+60 °C range.
What connection and load details should be checked?
Check the two-wire actuator connection, 750 Ω maximum load impedance with current outputs, and 800 m shielded maximum cable length.
What information is needed for a quotation?
Provide the required quantity and destination together with the complete order number.